41-2168. Fire protection systems;
definitions


A. All backflow prevention equipment installed on class 1 and class 2 fire
protection systems shall comply with state fire code standards.


B. Check valve assemblies installed on class 1 or class 2 fire protection systems
as backflow protection equipment pursuant to this section shall be inspected and
maintained in accordance with the procedures identified in the national fire protection
association publication 25 for water based fire protection systems, 1992 edition, to
determine compliance with the minimum design standards established by the state fire
code. Inspections of check valve assemblies installed on class 1 or class 2 fire
protection systems shall be performed on an annual basis with records of the inspections
provided to the local fire department and drinking water provider.


C. Any malfunction or abnormality with a check valve assembly installed on class 1
or class 2 fire protection systems shall be reported within twenty-four hours to the
local fire department and drinking water provider.


D. A fire code authority may establish guidelines for the installation of backflow
prevention equipment on a class 1 or class 2 fire protection system that exceeds the
minimum standards established by the state fire code if the backflow prevention equipment
is approved for use on class 1 or class 2 fire protection systems pursuant to section
1.102 of the uniform fire code, 1988 edition.


E. A fire code authority or a drinking water provider may require the installation
of backflow prevention equipment on class 1 and class 2 fire protection systems that
exceeds the minimum standards established by the state fire code if a special backflow
condition is identified. The use of nonpotable pipe in a fire protection system does not
by itself constitute a special backflow condition. The drinking water provider shall
consult with the fire code authority and provide the fire code authority with an
opportunity to comment before installing or requiring the installation of backflow
equipment that exceeds the minimum standards established by the state fire code.


F. For purposes of this section:


1. "Class 1 fire protection system" means a fire protection system that is directly
connected to a public water main and all sprinkler drains on the fire protection system
discharge into the atmosphere, dry wells or other safe outlets. Class 1 fire protection
system does not include a system that has a connection with pumps, tanks, reservoirs or
other water supplies, or a system that contains antifreeze or other additives.


2. "Class 2 fire protection system" means a class 1 fire protection system with
booster pumps installed in the connections from the street mains.


3. "Fire code authority" means the state fire marshal or the state fire marshal's
designee, except that for an incorporated city or town with a population of at least one
hundred thousand persons according to the most recent United States decennial census that
has adopted an ordinance pursuant to section 41-2163, subsection A, fire code authority
means the municipal fire chief or the fire chief's designee.


4. "Special backflow condition" means a condition that exists at the site of a
class 1 or class 2 fire protection system and that may present a contamination hazard to
the domestic water supply, including:


(a) Underground fire protection system lines that are parallel to and within six
feet horizontally of sewer lines or other lines carrying toxic materials.


(b) The use, storage or handling of materials on a site by a property owner or
occupant that could present a significant health hazard to the domestic water supply.


(c) The presence of unusually complex piping systems.


(d) Water supplied to a site or an area from either:


(i) Two or more services of a water utility.


(ii) Two different water utilities.


(iii) A supplemental water supply.