Section 125.565 - Tanks located underground.
FUEL OIL (EXCERPT)
Act 319 of 1929
125.565 Tanks located underground.
Act 319 of 1929
125.565 Tanks located underground.
Sec. 15.
Tanks located underground shall have the top of tank at least 3 feet below the surface of the ground, and below the level of the lowest pipe leading into the building to be supplied. Tanks may be permitted underneath a building if buried at least 3 feet below the lowest floor, or they may be placed 24 inches below the lowest floor and covered with 15 inches of earth and 9 inches of brick or concrete.
History: 1929, Act 319, Imd. Eff. May 28, 1929 ;-- CL 1929, 2622 ;-- CL 1948, 125.565