Grounding of frames, casings, and other electrical equipment.

Where grounding wires are used to ground metallic sheaths, armors, conduits, frames, casings and other metallic enclosures, such grounding wires must comply with the following conditions:

(1) The cross-sectional area (size) of the grounding wire shall be at least one-half the cross-sectional area (size) of the power conductor where the power conductor used is No. 6 A.W.G. or larger.

(2) Where the power conductor used is less than No. 6 A.W.G., the cross-sectional area (size) of the grounding wire shall be equal to the cross-sectional area (size) of the power conductor.

(Acts 1949, No. 207, p. 242, §41; Acts 1975, 4th Ex. Sess., No. 147, p. 2866, §1.)

State Codes and Statutes

Statutes > Alabama > Title25 > Chapter9 > 25-9-172

Section 25-9-172

Grounding of frames, casings, and other electrical equipment.

Where grounding wires are used to ground metallic sheaths, armors, conduits, frames, casings and other metallic enclosures, such grounding wires must comply with the following conditions:

(1) The cross-sectional area (size) of the grounding wire shall be at least one-half the cross-sectional area (size) of the power conductor where the power conductor used is No. 6 A.W.G. or larger.

(2) Where the power conductor used is less than No. 6 A.W.G., the cross-sectional area (size) of the grounding wire shall be equal to the cross-sectional area (size) of the power conductor.

(Acts 1949, No. 207, p. 242, §41; Acts 1975, 4th Ex. Sess., No. 147, p. 2866, §1.)

State Codes and Statutes

State Codes and Statutes

Statutes > Alabama > Title25 > Chapter9 > 25-9-172

Section 25-9-172

Grounding of frames, casings, and other electrical equipment.

Where grounding wires are used to ground metallic sheaths, armors, conduits, frames, casings and other metallic enclosures, such grounding wires must comply with the following conditions:

(1) The cross-sectional area (size) of the grounding wire shall be at least one-half the cross-sectional area (size) of the power conductor where the power conductor used is No. 6 A.W.G. or larger.

(2) Where the power conductor used is less than No. 6 A.W.G., the cross-sectional area (size) of the grounding wire shall be equal to the cross-sectional area (size) of the power conductor.

(Acts 1949, No. 207, p. 242, §41; Acts 1975, 4th Ex. Sess., No. 147, p. 2866, §1.)