State Codes and Statutes

Statutes > California > Fin > 13040-13041

FINANCIAL CODE
SECTION 13040-13041



13040.  (a) Each operator of an automated teller machine installed
on or after July 1, 1991, shall comply with Section 13041 commencing
on the date the automated teller machine is installed. Compliance
with Section 13041 by operators as to automated teller machines
existing as of July 1, 1991, shall be optional until July 1, 1993,
and mandatory thereafter. This subdivision shall apply to an operator
of an automated teller machine only to the extent that the operator
controls the access area or defined parking area to be lighted.
   (b) If an access area or a defined parking area is not controlled
by the operator of the automated teller machine, and if the person
who leased the automated teller machine site to the operator controls
the access area or defined parking area, the person who controls the
access area or defined parking area shall comply with Section 13041
as to any automated teller machine installed on or after July 1,
1991, commencing on the date the automated teller machine is
installed; and as to any automated teller machine existing as of July
1, 1991, no later than on July 1, 1993.


13041.  The operator, owner, or other person responsible therefor,
shall provide lighting during hours of darkness with respect to an
open and operating automated teller machine and any defined parking
area, access area, and the exterior of an enclosed automated teller
machine installation according to the following standards:
   (a) There shall be a minimum of 10 candlefoot power at the face of
the automated teller machine and extending in an unobstructed
direction outward five feet.
   (b) There shall be a minimum of two candlefoot power within 50
feet from all unobstructed directions from the face of the automated
teller machine. In the event the automated teller machine is located
within 10 feet of the corner of the building and the automated teller
machine is generally accessible from the adjacent side, there shall
be minimum of two candlefoot power along the first 40 unobstructed
feet of the adjacent side of the building.
   (c) There shall be a minimum of two candlefoot power in that
portion of the defined parking area within 60 feet of the automated
teller machine.

State Codes and Statutes

Statutes > California > Fin > 13040-13041

FINANCIAL CODE
SECTION 13040-13041



13040.  (a) Each operator of an automated teller machine installed
on or after July 1, 1991, shall comply with Section 13041 commencing
on the date the automated teller machine is installed. Compliance
with Section 13041 by operators as to automated teller machines
existing as of July 1, 1991, shall be optional until July 1, 1993,
and mandatory thereafter. This subdivision shall apply to an operator
of an automated teller machine only to the extent that the operator
controls the access area or defined parking area to be lighted.
   (b) If an access area or a defined parking area is not controlled
by the operator of the automated teller machine, and if the person
who leased the automated teller machine site to the operator controls
the access area or defined parking area, the person who controls the
access area or defined parking area shall comply with Section 13041
as to any automated teller machine installed on or after July 1,
1991, commencing on the date the automated teller machine is
installed; and as to any automated teller machine existing as of July
1, 1991, no later than on July 1, 1993.


13041.  The operator, owner, or other person responsible therefor,
shall provide lighting during hours of darkness with respect to an
open and operating automated teller machine and any defined parking
area, access area, and the exterior of an enclosed automated teller
machine installation according to the following standards:
   (a) There shall be a minimum of 10 candlefoot power at the face of
the automated teller machine and extending in an unobstructed
direction outward five feet.
   (b) There shall be a minimum of two candlefoot power within 50
feet from all unobstructed directions from the face of the automated
teller machine. In the event the automated teller machine is located
within 10 feet of the corner of the building and the automated teller
machine is generally accessible from the adjacent side, there shall
be minimum of two candlefoot power along the first 40 unobstructed
feet of the adjacent side of the building.
   (c) There shall be a minimum of two candlefoot power in that
portion of the defined parking area within 60 feet of the automated
teller machine.


State Codes and Statutes

State Codes and Statutes

Statutes > California > Fin > 13040-13041

FINANCIAL CODE
SECTION 13040-13041



13040.  (a) Each operator of an automated teller machine installed
on or after July 1, 1991, shall comply with Section 13041 commencing
on the date the automated teller machine is installed. Compliance
with Section 13041 by operators as to automated teller machines
existing as of July 1, 1991, shall be optional until July 1, 1993,
and mandatory thereafter. This subdivision shall apply to an operator
of an automated teller machine only to the extent that the operator
controls the access area or defined parking area to be lighted.
   (b) If an access area or a defined parking area is not controlled
by the operator of the automated teller machine, and if the person
who leased the automated teller machine site to the operator controls
the access area or defined parking area, the person who controls the
access area or defined parking area shall comply with Section 13041
as to any automated teller machine installed on or after July 1,
1991, commencing on the date the automated teller machine is
installed; and as to any automated teller machine existing as of July
1, 1991, no later than on July 1, 1993.


13041.  The operator, owner, or other person responsible therefor,
shall provide lighting during hours of darkness with respect to an
open and operating automated teller machine and any defined parking
area, access area, and the exterior of an enclosed automated teller
machine installation according to the following standards:
   (a) There shall be a minimum of 10 candlefoot power at the face of
the automated teller machine and extending in an unobstructed
direction outward five feet.
   (b) There shall be a minimum of two candlefoot power within 50
feet from all unobstructed directions from the face of the automated
teller machine. In the event the automated teller machine is located
within 10 feet of the corner of the building and the automated teller
machine is generally accessible from the adjacent side, there shall
be minimum of two candlefoot power along the first 40 unobstructed
feet of the adjacent side of the building.
   (c) There shall be a minimum of two candlefoot power in that
portion of the defined parking area within 60 feet of the automated
teller machine.