52:27D-217.  Unattended terminal;  additional requirements
    In addition to the requirements specified in section 2 of this act, each unattended terminal at which a tank filled by pipeline is located shall comply with the following requirements:

    a.  The high level alarm system shall be capable of automatically shutting off or diverting the flow of the flammable liquid at the point of origin within  the terminal or at the point of receipt into the aboveground liquid storage  tank.

    b.  The high level alarm system shall be capable of automatically shutting off or diverting the flow of the flammable liquid at the point of origin within  the terminal or at the point of receipt into the aboveground liquid storage  tank in the event of a power failure in the high level alarm system.

     L.1984, c. 31, s. 4, eff. Nov. 1, 1984.

State Codes and Statutes

Statutes > New-jersey > Title-52 > Section-52-27d > 52-27d-217

52:27D-217.  Unattended terminal;  additional requirements
    In addition to the requirements specified in section 2 of this act, each unattended terminal at which a tank filled by pipeline is located shall comply with the following requirements:

    a.  The high level alarm system shall be capable of automatically shutting off or diverting the flow of the flammable liquid at the point of origin within  the terminal or at the point of receipt into the aboveground liquid storage  tank.

    b.  The high level alarm system shall be capable of automatically shutting off or diverting the flow of the flammable liquid at the point of origin within  the terminal or at the point of receipt into the aboveground liquid storage  tank in the event of a power failure in the high level alarm system.

     L.1984, c. 31, s. 4, eff. Nov. 1, 1984.

State Codes and Statutes

State Codes and Statutes

Statutes > New-jersey > Title-52 > Section-52-27d > 52-27d-217

52:27D-217.  Unattended terminal;  additional requirements
    In addition to the requirements specified in section 2 of this act, each unattended terminal at which a tank filled by pipeline is located shall comply with the following requirements:

    a.  The high level alarm system shall be capable of automatically shutting off or diverting the flow of the flammable liquid at the point of origin within  the terminal or at the point of receipt into the aboveground liquid storage  tank.

    b.  The high level alarm system shall be capable of automatically shutting off or diverting the flow of the flammable liquid at the point of origin within  the terminal or at the point of receipt into the aboveground liquid storage  tank in the event of a power failure in the high level alarm system.

     L.1984, c. 31, s. 4, eff. Nov. 1, 1984.